主内容区
Products Your location:Home > Dual-temperature control unit with hot and cold
Dual-temperature control unit with hot and cold
Product Description
Unit features and functions:
★ can be needed for the production of recycled water for cooling equipment to provide water for cooling or warming, at the same time can be in a constant temperature between ± 2 ℃, one-touch operation, convenient conversion, or to temperature faster.
Featured
★ electrical parts selected international brands, "Schneider" original product.
★ comprehensive protection measures, intelligent fault indication, beep alarm, a high degree of automation without special operation.
Hot and cold temperature of dual-use technology parameters (PU only)
|
Project Model |
DX-3M |
DX-5M |
DX-8M |
DX-10M |
DX-12M |
DX-15M | |
|
Cooling capacity |
Kcal/h |
6803 |
11094 |
17604 |
22188 |
25146 |
35500 |
|
KW |
7.91 |
12.9 |
20.47 |
25.8 |
29.24 |
41.28 | |
|
Enter the total powerKW |
9.33 |
14.8 |
21.25 |
22.37 |
29.58 |
33.82 | |
|
Power Supply |
3PH-380V-50HZ | ||||||
|
Refrigerants |
Name |
R22 | |||||
|
Control |
Capillary |
Outside the balanced thermal expansion valve | |||||
|
Compressor |
Type |
Scroll closed (piston type) | |||||
|
Power(KW) |
2.8 |
4.66 |
7.95 |
8.85 |
9.98 |
13.62 | |
|
Condenser |
Type |
Sets of high-performance aluminum finned copper-style + low-noise external rotor fan | |||||
|
Cooling air volume(m3/h) |
3000 |
5000 |
8000 |
10000 |
12000 |
15000 | |
|
Evaporator |
Type |
Tank coil (shell and tube) | |||||
|
Frozen waterm3 |
1.36 |
2.22 |
3.52 |
4.44 |
5.03 |
7.1 | |
|
Water tank capacityL |
50 |
70 |
120 |
200 |
200 |
270 | |
|
Diameter and out of water |
1″ |
1″ |
1″ |
1-1/2″ |
1-1/2″ |
2″ | |
|
Pumps |
Power(KW) |
0.37 |
0.75 |
0.75 |
0.75 |
1.1 |
1.5 |
|
Head(M) |
20 |
20 |
22 |
20 |
20 |
20 | |
|
Heating device |
Heating tube | ||||||
|
Power(KW) |
6 |
9 |
12 |
12 |
18 |
18 | |
|
Security protection |
Compressor overheat protection, overcurrent protection, high and low pressure protection, over-temperature protection, traffic protection, phase sequence / lack of protection, exhaust overheating protection, antifreeze protection. | ||||||
|
Overall dimensions |
long(MM) |
930 |
1140 |
1300 |
1530 |
1680 |
1800 |
|
wide(MM) |
520 |
560 |
720 |
760 |
810 |
990 | |
|
high(MM) |
975 |
1040 |
1350 |
1470 |
1280 |
1680 | |
|
Machine weight |
Kg |
135 |
175 |
320 |
450 |
530 |
750 |