Product Description
Features:
Excellent, outstanding cooling heart:
The heart of the system, one system using a high refrigeration compressor efficiency, high-performance closed-wide import compressors for high-performance products, economic, reliable and quiet operation of refrigeration systems, compressors and internal settings are missing and the overload of protection devices for product quality and provide a reliable guarantee for life.
Large air volume, low noise:
High-quality centrifugal fan, so that a large quantity of products with the wind, high wind pressure, stable performance, low noise.
Efficient Condenser:
The use of countercurrent shell and tube condenser design, internal brass tube imported, just with less water, will be able to achieve highly efficient heat exchange properties, thereby increasing the heat dissipation.
Good and stable operation of the refrigerant:
Some housing units were segregated, so that the compressor noise and isolated from the outside world, greatly reduced the unit running the noise and provide a quiet environment, heat insulation Owens on imported cotton, and cut off from the heat exchange with the outside world to prevent the unit surface, "a Khan ", greatly reduced the unit's noise and improve the performance of refrigeration units.
The heart of the system, one system using a high refrigeration compressor efficiency, high-performance closed-wide import compressors for high-performance products, economic, reliable and quiet operation of refrigeration systems, compressors and internal settings are missing and the overload of protection devices for product quality and provide a reliable guarantee for life.
Large air volume, low noise:
High-quality centrifugal fan, so that a large quantity of products with the wind, high wind pressure, stable performance, low noise.
Efficient Condenser:
The use of countercurrent shell and tube condenser design, internal brass tube imported, just with less water, will be able to achieve highly efficient heat exchange properties, thereby increasing the heat dissipation.
Good and stable operation of the refrigerant:
Some housing units were segregated, so that the compressor noise and isolated from the outside world, greatly reduced the unit running the noise and provide a quiet environment, heat insulation Owens on imported cotton, and cut off from the heat exchange with the outside world to prevent the unit surface, "a Khan ", greatly reduced the unit's noise and improve the performance of refrigeration units.
|
Model |
DS-08S |
DS-10S |
DS-15D |
DS-20D |
DS-25D |
DS-30D |
DS-40T |
DS-50F |
DS-60F | ||||
|
DSR-08S |
DSR-10S |
DSR-15D |
DSR-20D |
DSR-25D |
DSR-30D |
DSR-40T |
DSR-50F |
DSR-60F | |||||
|
Co |
Kcal/h |
21500 |
29000 |
43000 |
58000 |
71700 |
85400 |
114400 |
143400 |
170800 | |||
|
Electric heat |
W |
15000 |
20000 |
28000 |
44000 |
48000 |
60000 |
78000 |
98000 |
126000 | |||
|
Power Supply |
3PH 380V 50Hz | ||||||||||||
|
Input power |
kW |
6 |
8 |
13.2 |
18 |
22.5 |
27.5 |
37 |
44.5 |
55 | |||
|
Operating current |
A |
14.3 |
20 |
28.1 |
42.4 |
46 |
53 |
73 |
94.6 |
106 | |||
|
Compressor |
Type |
Closed piston | |||||||||||
|
Power x number |
HP |
7.5 |
10 |
7.5×2 |
10×2 |
10+15 |
15×2 |
10+15×2 |
10×2+15×3 |
15×4 | |||
|
Fans |
Type |
Centrifugal External Rotor |
Belt drive centrifugal | ||||||||||
|
Magnitude |
1(2) |
1(2) |
2 |
2 |
2 |
2 |
2 |
2 |
2 | ||||
|
Power |
kW |
0.45(0.5) |
0.55(0.5) |
2.2(0.74) |
3.0 |
4.0 |
5.5 |
7.5 |
11 |
11 | |||
|
Air volume |
CFM |
2350 |
3000 |
4600 |
6250 |
7630 |
9170 |
13000 |
17000 |
20000 | |||
|
CMH |
4000 |
5100 |
7800 |
10600 |
13000 |
15600 |
22140 |
27700 |
33500 | ||||
|
Amount of outside pressure |
Pa |
250(0) |
250(0) |
260(0) |
300 |
350 |
380 |
400 |
450 |
500 | |||
|
Noise |
dB(A) |
≤62 |
≤62 |
≤65 |
≤68 |
≤70 |
≤70 |
≤75 |
≤76 |
≤78 | |||
|
Condenser |
Type |
Shell and tube | |||||||||||
|
m3/h |
5.8 |
7.5 |
11.5 |
15 |
19 |
22.2 |
30 |
37.5 |
44.5 | |||
|
Diameter of the cooling water |
in |
1-1/2″ |
2″ |
2-1/2″ |
3″ | ||||||||
|
Condensate drain diameter |
in |
1″ |
1-1/4″ | ||||||||||
|
Outlet diameter |
in |
3/4″ | |||||||||||
|
Dimensions |
long |
mm |
960 |
1200 |
1700 |
1700 |
1880 |
1880 |
2050 |
2450 |
2450 | ||
|
wide |
mm |
560 |
600 |
600 |
750 |
1090 |
1090 |
1300 |
1300 |
1300 | |||
|
high |
mm |
1740 |
1740 |
1880 |
1880 |
1920 |
1920 |
1920 |
1990 |
1990 | |||
|
Unit weight |
kg |
380 |
430 |
500 |
550 |
750 |
780 |
1250 |
1560 |
1630 | |||
* The above products continuous improvement and innovation, and specifications are subject to change without notice after updating. Can be customized according to customer requirements models.